Technical charasteristics

Control cabinet for 4 valves
  • Dimensions 800 x 600 x 300 mm (W x H x D)
  • Protection cIass IP65
Hand pump
  • Double acting hand pump with pilot check valves
  • Fluid viscosity: 10−500 mm2 /s
  • Filtration: ISO code 16/13; SAE class 4 or better
  • Fluid temperature: −20 °C − +80 °C
  • Ambient temperature: −20 °C − +50 °C
  • Max. pressure: 380 bar
  • Pressure limiter: 200 bar (adjustable)
Oil tank
  • Reservoir capacity: 5 l

Control valve block
  • Control valves: 4 / 6 pcs.
  • Max. pressure: 350 bar
  • Positions of lever: 3 (Valve open – Neutral – Valve shut)
  • It's possiböe to maneuver one valve at a time.
Pressure gauge
  • Range: 0…315 bar
Indicator lamp panel
  • Indicated open and shut positions of valves
  • Low voltage powered
  • Connected to position transmitter on actuator
Connection for portable pump unit
  • Quick couplings with flat face casing
  • Pump unit (sold separately) incl. transportation box, hydraulic hoses and electric cable